All labels with text shall be in English.
Anti-Condensation Heaters
The Panel shall be provided with a thermostat controlled anti-condensation heater 240 V, 50 Hz.
Earthing System
All normal non-current carrying metal parts of the panel and associated components shall be bonded to a common copper
earthbar running the entire length inside the switchboard.
The earthbar shall be located in the lower part of the frame work and provided with two termination points for
connection to the main earthing grid.
2.5 Ignition Oil Supply
MEDICAL WASTE INCINERATOR INTALI8ATION
Design, Supply, install, test and commission medical waste
Incinerator as per the attached specification. The price shall
include all accessories including the civil work and spare part
list to make the system complete.
incinerator burning capacity-250kg/hr NO 1
Jimma University Referal Hospital
Incinerator
Medical Waste Incinerator
Purpose
For a complete destruction of waste from various hospital services by heat treatment of high temperature in accordance
with EU standard on emission requirement
Waste from health care activities
Infections waste, laboratory cultures, waste form operation room isolations material in contact with infected
patients, waste potentially being infected by pathogenic agents.
Pathological waste, human fragments, bold, fetus, all body fluids, human tissues.
Sculpts, needles, infusion sets, blades, glass
Pharmaceutical waste.
Chemical waste laboratory reagents, disinfectants
Expired drugs.
Low radiation radioactive element.
Medical waste incinerator: – Ecological Requirement
-No odor
-No fume
-Definitive treatment of waste
Medical waste incinerator: – Manufacturing Standards
-UL, CE, ASME, ISA EURO emission standard
1.Medical waste incinerator
Construction- CS plate shells, FB reinforcement, caste refractory linings,
insulation and 14 gage aluminum jacket.
Type of fuel- Oil fired (Diesel)
Burning Capacity- 250kg/hr and moisture up to 80%
Duration-8-16/Continuous
Average fuel consumption- Very little as much as possible
Control Type- PLC based operation
Operating Temperature- Primary chamber 800c± 50
– Secondary Chamber 1050c ± 50
Size of incinerator – Not more than 15mx7.20m
Chimney – Q630x25meter height and 7mm thick CS.
Combustion efficiency – 99%
Mode of waste handling – Semi- Automatic via ram loader.
Mode of ash handling – Semi- automatic via grate and ash trolley.
Pollution control equipment- Dry settlement zone
Doors – 1- waste charging door in primary chamber
1-Clinker door in primary chamber
1-Ash trolley access door in primary chamber
1-Clean out door in secondary chamber
Burner -2- ignition burner in primary chamber
2-after burner in secondary chamber.
Type- package mono block-fully automatic
Type of burner operation- modulation control
Forced draught fan- 1- primary air fan
1-secondary air fan
Fuel storage tank- Capacity-2500liter above grond
– Material -6mm thick mild steel
-2-diesel pump, gate valve, sfety valve, strainer
pipe, pressure gage, check valve, control board
Level indicator. Etc
Refractory/insulation thickness- not less than 225mm
Ram loader capacity-0.75m3
Electrical supply -380v/3ph/50 Hz
Finish and painting type- powder coated
Audio/Visual alarm system- burner lockout, overload fault
Electrical accessories – primary and secondary chamber temperature
Controller /indicator, auto controls, electrical
Control switches, push buttons, relays contavtors
Thermocouples, burner sequence controllers,
Timers, emergency stop and alarms.